Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00275774 Renewal 10/15/2025 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.110(b)There was no smoke detector within 15 feet of either bedroom. The closest smoke detector was approximately 20 feet away from the first bedroom, and approximately 31 feet away from the second bedroom.There shall be an operable automatic smoke detector located within 15 feet of each individual and staff bedroom door. On October 16, 2025, the fire safety trainer installed a smoke detector in the hallway 15 feet from the individual's bedroom door, ensuring full compliance with 6400.110(b). The detector was tested at the time of installation to confirm functionality and proper alarm response. 10/16/2025 Implemented