Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00243107 Initial review 04/25/2024 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6500.107(a)There was no smoke detector located within the home's attic at the time of inspection.A home shall have a minimum of one operable automatic smoke detector provided on each floor, including the basement and attic.The Prospective Life-sharing Provider¿s Maintenance worker installed a smoke detector in the attic of the home. 04/30/2024 Implemented
6500.108(a)There was no fire extinguisher located within the home's attic at the time of inspection.There shall be at least one operable fire extinguisher with a minimum 2-A rating for each floor, including the basement and attic.The Prospective Life-sharing Provider¿s Maintenance worker placed a 5lb fire extinguisher with the required 2A rating in the attic. The fire extinguisher was checked and labeled by Kistler O¿brien. 04/30/2024 Implemented