| 6400.110(e) | At the time of the 07/23/25 inspection, the alarms on all three levels functioned independently but did not activate the other alarms when tested. | If the home serves four or more individuals or if the home has three or more stories including the basement and attic, there shall be at least one smoke detector on each floor interconnected and audible throughout the home or an automatic fire alarm system that is audible throughout the home. The requirement for homes with three or more stories does not apply to homes licensed in accordance with this chapter prior to November 8, 1991. | This citation occurred due to a transmission issue with the current interconnected system. One detector had a frequency not allowing it to receive a signal correctly.Director has order new interconnected smoke detectors. These will be placed appropriately within this home and tested by 8.1.25 |
08/01/2025
| Implemented |