Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00264232 Renewal 04/01/2025 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.66There is no operable light fixture outside of the rear exit to ensure safety and avoid accidents.Rooms, hallways, interior stairways, outside steps, outside doorways, porches, ramps and fire escapes shall be lighted to assure safety and to avoid accidents. The outside rear operable light has been fixed 04/30/2025 Implemented
6400.67(b)The electrical outlet in the dining room is inoperable. Floors, walls, ceilings and other surfaces shall be free of hazards.The electrical outlet in the dining room has been fixed. 04/30/2025 Implemented
6400.68(b)The running water in both the kitchen and bathroom returned with temperatures exceeding the allowable threshold; 131.8F and 137.5 respectively. Hot water temperatures in bathtubs and showers may not exceed 120°F. The water temperature in both the kitchen and the bathroom has been reduced to the normal 120 degrees 04/30/2025 Implemented
6400.76(a)The seating accommodations in the dining room are not sturdy and presents a potential hazard. Furniture and equipment shall be nonhazardous, clean and sturdy. The dining chairs has been replaced 04/30/2025 Implemented
6400.101The kitchen door requires a key to exit which poses a fire safety hazard.Stairways, halls, doorways, passageways and exits from rooms and from the building shall be unobstructed. The kitchen door has been restored 04/30/2025 Implemented
6400.111(f)The fire extinguishers in the home do not have tags indicating that they have been inspected/approved by a fire safety expert. A fire extinguisher shall be inspected and approved annually by a fire safety expert. The date of the inspection shall be on the extinguisher. The fire extinguishers have been inspected and tagged. 04/30/2025 Implemented