Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00210488 Renewal 08/12/2022 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.101The lock on the side door that leads outside had a keylock on the interior. In the event of a fire evacuation the door needs to be able to open without a key.Stairways, halls, doorways, passageways and exits from rooms and from the building shall be unobstructed. During licensing inspection on 8/12/2022, the key lock to the side door was found to be obstructive. A contractor was hired to replace the lock on the same day. The lock was replaced with a keyless system on 8/13/2022 to ensure the exit is unobstructed at all times in compliance with 55 PA Code Chapter 6400.101 08/16/2022 Implemented
6400.106There were no documentation of furnace inspections or cleanings having occurred in the home.Furnaces shall be inspected and cleaned at least annually by a professional furnace cleaning company. Written documentation of the inspection and cleaning shall be kept. During licensing inspection on 8/12/2022, the annual furnace inspection had only been scheduled. The furnace inspection was completed on 8/16/22 by a professional furnace company, and the home passed the inspection. The written documentation of the inspection and cleaning completed on 8/16/22 is kept for the records. 08/16/2022 Implemented
SIN-00173937 Initial review 07/10/2020 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.110(e)The home had 3 levels, main floor, second floor and basement, and the smoke detectors were not interconnected.If the home serves four or more individuals or if the home has three or more stories including the basement and attic, there shall be at least one smoke detector on each floor interconnected and audible throughout the home or an automatic fire alarm system that is audible throughout the home. The requirement for homes with three or more stories does not apply to homes licensed in accordance with this chapter prior to November 8, 1991. Agnew House Record of Plan of Correction-7/10/2020 LIS 1. The Plan to fix the immediate problem The VP Operations requested a contractor to replace the broken smoke detectors with functionally interconnected smoke detectors. New interconnected smoke detectors are needed, one to be placed on each level of the home. After learning that Agnew House smoke detectors are inoperable, the VP of Operations hired a qualified contractor to replace the inoperative smoke detectors. The three interconnected smoke detectors, one on each level of the home was replaced the same day, 7/10/2020 when it was found to be inoperable 2. A plan to prevent future occurrences Every month, staff will check and document the operability of the home¿s interconnected smoke detectors as part of monthly fire drills. Two HHHS policies (1) Fire Drills and 2) Smoke dectectors_Fire Alarms_Inoperable policy, along with HHHS fire drill forms, will serve as the framework to prevent future occurrences. These policies outline a process of monthly assessment of the operability of the smoke detectors. The fire Drill forms serve as a record of compliance 07/10/2020 Implemented
SIN-00249766 Renewal 08/13/2024 Compliant - Finalized
SIN-00230681 Renewal 08/21/2023 Compliant - Finalized
SIN-00191474 Renewal 09/18/2021 Compliant - Finalized